EVALUATION OF CONCRETE ANCHOR BOLTS

THE STUDY WAS CONDUCTED TO DETERMINE THE EFFECTIVENESS OF VARIOUS TYPES OF CONCRETE ANCHORAGE DEVICES. THIS WAS TO BE ACCOMPLISHED BY COMPARING THE AXIAL PULLOUT STRENGTHS OF CAST-IN-PLACE BOLTS AND FRICTION ANCHORS. STATIC AXIAL LOAD TESTS WERE CONDUCTED ON CAST-IN-PLACE BOLTS, EPOXIED AND GROUTED-IN-PLACE THREADED RODS, AND 7 TYPES (5 BRANDS) OF COMMERCIALLY AVAILABLE FRICTION TYPE CONCRETE ANCHORAGE DEVICES. CONSTANT AXIAL LOAD TESTS WERE CONDUCTED ON THE EPOXIED-IN-PLACE THREADED RODS AND ALL OF THE FRICTION TYPE ANCHORS. IT WAS FOUND THAT THE STRENGTH OF EPOXIED AND GROUTED-IN-PLACE RODS AND OF COMMERCIAL FRICTION TYPE ANCHORS WAS DEPENDENT ON THE LOADING RATE, WHEREAS THE STRENGTH OF CAST-IN-PLACE BOLTS WAS INDEPENDENT OF THE LOADING RATE. BECAUSE OF THIS, IT WAS NOT POSSIBLE TO OBTAIN A DIRECT CORRELATION BETWEEN STATIC AXIAL PULLOUT STRENGTHS OF CAST-IN-PLACE BOLTS AND THE OTHER TYPES OF ANCHORS TESTED. PERFORMANCE CHARACTERISTICS AND TEST RESULTS FOR EACH TYPE OF ANCHORAGE DEVICE ARE DISCUSSED INDIVIDUALLY. /AUTHOR/