THE SCALE METER: A NEW METHOD FOR DETERMINING THE CRITICAL PH OF SCALING
A new understanding of the Saturation Index is presented which leads to the concept of a critical pH, the true pH of scaling. The critical pH is about 1.7 to 2.0 pH units higher than the pH of saturation predicted by the index. The method of determining the critical pH is described as a continuous controller which utilizes this theory. The application of the controller to cooling water systems is described for several chemical treatment programs, and controller results are given.
-
Corporate Authors:
National Association of Corrosion Engineers
2400 West Loop South
Houston, TX United States 77027 -
Authors:
- Feitler, H
- Publication Date: 1971-2
Media Info
- Features: Figures; References;
- Pagination: p. 31-35
-
Serial:
- Materials Protection and Performance
- Volume: 11
- Issue Number: 1
- Publisher: National Association of Corrosion Engineers
Subject/Index Terms
- TRT Terms: Corrosion protection; pH value
- Old TRIS Terms: Boiler water treatment
- Subject Areas: Construction; Marine Transportation; Materials;
Filing Info
- Accession Number: 00028646
- Record Type: Publication
- Source Agency: United States Merchant Marine Academy
- Files: TRIS
- Created Date: Apr 10 1973 12:00AM