RADIOFREQUENCY INTERFERENCE/ELECTROMAGNETIC INTERFERENCE MEASUREMENTS. OAKLAND AIR ROUTE TRAFFIC CONTROL CENTER

The report describes electromagnetic interference tests at the Oakland Air Route Traffic Control Center (ARTCC), Oakland, California. The tests included measurement of radiated and conducted emission from both the automated system and non-automated equipments, and radiated and conducted susceptibility of the automated system. Conducted and radiated electric and magnetic field emission from most of the automated system equipments exceeded the limits of MIL-STD-461A, but was not sufficiently high to adversely affect other equipment certified to MIL-STD-461A. Most of the automated system equipments met the susceptibility limits of MIL-STD-461A. Exceptions were the Plan View Display, Common Logic Unit, Tape Drive, M1 display and System Control Console. (Modified author abstract)

  • Corporate Authors:

    NATIONAL AVIATION FACILITIES EXPERIMENTAL CENTER

    ATLANTIC CITY, NJ  United States 
  • Authors:
    • Stone, M V
  • Publication Date: 1974-5

Media Info

  • Pagination: 220 p.

Filing Info

  • Accession Number: 00057386
  • Record Type: Publication
  • Source Agency: National Technical Information Service
  • Report/Paper Numbers: FAA-NA-74-150 Final Rpt.
  • Contract Numbers: DOT-FA72NA-728
  • Files: NTIS
  • Created Date: Nov 6 1974 12:00AM